PVC-insulated wire is the most common cable in any building. Single cores in conduit, flat twin cords, appliance flex. Most of it is made to IEC 60227, and it carries type names like 60227 IEC 01 or 60227 IEC 53. Above 1 kV, the test regime changes completely; see our IEC 60502-2 cable tests guide for MV cable.
The tests behind that wire are simple, but the numbers on the reports confuse people. A minimum insulation resistance of 0.011 MΩ·km looks like a typo to anyone used to reading hundreds of megohms on a megger. It isn’t a typo.
This article goes through the test report line by line. What each test does, the conditions, and how to read the result.
Table of Contents
Which Standards Apply
Two documents work together:
- IEC 60227 sets the cable requirements. Part 1 has the general rules, and Parts 3 onward cover specific cable types. Part 1 is now in its 2024 edition.
- IEC 63294:2021 sets the test methods. It replaced IEC 60227-2, which was withdrawn in 2021. It also replaced the matching test-method parts for rubber cables (IEC 60245-2) and two other cable families.
So a current test report should cite IEC 63294 for methods. An older report citing IEC 60227-2 isn’t wrong for its date, but a new specification should reference IEC 63294.
The methods carried over closely. The 2024 edition of IEC 60227-1 lists only two significant technical changes: the switch from IEC 60227-2 to IEC 63294, and updated references.
Ratings and Compounds
Rated Voltage
PVC wiring cables are rated Uo/U:
- Uo is the RMS voltage between conductor and earth (a metal covering or the surrounding medium).
- U is the RMS voltage between conductors.
The three ratings are 300/300 V, 300/500 V and 450/750 V.
On AC, both Uo and U must be at least equal to the system’s nominal voltage. On DC, the system’s nominal voltage must not be higher than 1.5 times the cable’s rated voltage.
A system can run up to 10% above its nominal voltage permanently. The cable is fine with that, as long as its rating meets the nominal voltage.
Insulation Compound Types
| Type | Use |
|---|---|
| PVC/C | Cables for fixed installation |
| PVC/D | Flexible cables |
| PVC/E | Heat-resistant cables for internal wiring |
The type isn’t a recipe. It’s a category set by test performance. Two PVC/C compounds can have different formulations and both pass.
Type Tests and Sample Tests
Every test in the cable tables is marked T (type test) or S (sample test), or both.
- Type tests are done before a cable type is sold commercially. They aren’t repeated unless the materials or design change in a way that could affect performance.
- Sample tests are done on finished cable to check that production still matches the design.
Before Any Test
A few general rules apply across the board:
- Wait after extrusion. Tests start no earlier than 16 hours after the insulation or sheath was extruded.
- Ambient temperature unless a test says otherwise.
- AC test voltage is 49 Hz to 61 Hz, roughly sinusoidal, with a peak-to-RMS ratio of √2 ± 7%. Values are RMS.
- Multicore cables: no more than three cores are tested (different colours where possible), except for the thickness check.
- Relief markings: if there’s raised marking on the insulation or sheath, the samples must include it. Raised marking makes a local thin spot, so it has to be tested.
Line 1: Conductor Resistance
This is a sample of at least 1 m. Measure each conductor and the exact length, then correct to 20 °C and 1 km:
R20 = Rt × 254.5 / (234.5 + t) × 1000 / L
- R20 is the resistance at 20 °C, in Ω/km
- Rt is the measured resistance of L metres at t °C, in Ω
- L is the sample length in metres (the cable length, not the length of a stranded wire)
The result must not exceed the IEC 60228 maximum for that conductor class and size.
This is a copper test, not an insulation test. But undersized copper is the most common way cheap wire fails a report, so it sits at the top for a reason.
Line 2: Voltage Test on the Completed Cable
This checks the whole cable, sheath and all.
Setup:
- Sample length: at least 10 m
- If the cable has no metal layer, soak it in water for at least 1 hour at 20 °C ± 5 °C
Sequence:
- Voltage between each conductor and all the others, connected together and to the water (or metal layer).
- Then voltage between all conductors connected together and the water (or metal layer).
Levels:
| Rating | Voltage (AC) | Time per application |
|---|---|---|
| 300/300 V | 2000 V | 5 min |
| 300/500 V | 2000 V | 5 min |
| 450/750 V | 2500 V | 5 min |
Pass: no breakdown.
The water is the electrode. It reaches every bit of the outer surface, so a pinhole or thin spot anywhere along the 10 m gets stressed. A metal plate or foil would miss gaps.
Line 3: Voltage Test on Cores
This applies to sheathed cables and flat non-sheathed cords (not flat tinsel cords). It tests each core’s own insulation, with the sheath out of the way.
Setup:
- Take 5 m of cable.
- Remove the sheath, fillers and any other covering without damaging the cores.
- For flat non-sheathed cords, nick the insulation between cores and pull them apart by hand for 2 m.
- Soak the cores in water for at least 1 hour at 20 °C ± 5 °C.
Voltage goes between the conductors and the water.
Levels:
| Rating | Insulation thickness | Voltage (AC) | Time |
|---|---|---|---|
| 300/300 V, 300/500 V | Up to 0.6 mm | 1500 V | 5 min |
| 300/300 V, 300/500 V | Over 0.6 mm | 2000 V | 5 min |
| 450/750 V | Any | 2500 V | 5 min |
Pass: no breakdown.
Why test both ways? The sheath adds insulation. A core with a weak spot can hide inside a good sheath on the completed-cable test. Stripped and in water, it can’t.
Line 4: Insulation Resistance (Hot, in Water)
This is the line that confuses people.
Setup:
- Use the 5 m core samples that already passed Line 3 (or Line 2 if Line 3 doesn’t apply).
- Soak them in water already heated to the specified temperature for at least 2 hours.
- Keep about 0.25 m at each end above the water.
The water temperature is set by the cable’s own part of IEC 60227. For general-purpose 70 °C wire like 60227 IEC 01, the minimums in the cable tables are given at 70 °C.
Measurement:
- Apply 80 V to 500 V DC between conductor and water.
- Read at 1 minute.
- Convert the reading to MΩ·km.
Why the Numbers Are So Small
Here are typical minimums for 60227 IEC 01 single-core wire, as listed in manufacturers’ datasheets:
| Size | Conductor | Insulation | Minimum IR at 70 °C |
|---|---|---|---|
| 1.5 mm² | Solid | 0.7 mm | 0.011 MΩ·km |
| 1.5 mm² | Stranded | 0.7 mm | 0.010 MΩ·km |
| 2.5 mm² | Solid | 0.8 mm | 0.010 MΩ·km |
| 4 mm² | Solid | 0.8 mm | 0.0085 MΩ·km |
| 6 mm² | Solid | 0.8 mm | 0.0070 MΩ·km |
| 10 mm² | Solid | 1.0 mm | 0.0070 MΩ·km |
0.011 MΩ·km is 11 kΩ for a full kilometre. That looks terrible until you see the conditions. The insulation is at 70 °C, fully wet on the outside, with water as the outer electrode over the entire surface.
PVC’s resistivity falls hard with temperature, which is why an insulation resistance reading always needs its temperature. A hot, wet test is a worst case on purpose. It finds compound and process problems, and it isn’t meant to mimic a dry installed circuit at room temperature.
The minimums come straight from a formula:
R = 0.0367 × log10(D/d)
- R is in MΩ·km
- D is the nominal outer diameter of the insulation
- d is the diameter of the circle around the conductor
The 0.0367 factor corresponds to a volume resistivity of 1 × 10⁸ Ω·m. Every value in the table is that one resistivity, applied to each cable’s geometry. Thicker insulation relative to the conductor gives a higher minimum.
Converting MΩ·km to a Real Length
Insulation resistance falls as length grows, because more length means more parallel leakage paths. To get the minimum for an actual sample:
R_sample = R_km / length in km
For 100 m of 1.5 mm² solid wire at 70 °C in water:
0.011 / 0.1 = 0.11 MΩ, which is 110 kΩ.
For the 5 m test sample, it’s 0.011 / 0.005 = 2.2 MΩ.
So a lab seeing 2.2 MΩ on a 5 m hot core sample is right at the limit. A field technician seeing 2.2 MΩ on a dry 100 m circuit at 20 °C is looking at something very different. Don’t carry factory MΩ·km values into field acceptance, or the other way round. Field verification of installations uses its own limits and conditions.
For more on how length, temperature and geometry move a reading, see our insulation resistance formula and temperature correction guides.
Line 5: Insulation Thickness
Electrical tests catch failures. Thickness catches cables that pass today but have no margin.
Sampling:
- Take three pieces from three places at least 1 m apart.
- Check every core on cables with up to five cores, and any five cores on cables with more.
Evaluation:
- The mean of the readings from the three pieces of each core, rounded to 0.1 mm, must be at least the specified value.
- The minimum at any point may be below the specified value, but by no more than 0.1 mm + 10% of the specified value.
Example: 2.5 mm² wire, specified 0.8 mm
- Mean must be at least 0.8 mm.
- Minimum allowed: 0.8 − (0.1 + 0.08) = 0.62 mm.
Example: 1.5 mm² wire, specified 0.7 mm
- Mean must be at least 0.7 mm.
- Minimum allowed: 0.7 − (0.1 + 0.07) = 0.53 mm.
The two rules work together. A cable with the right average can still be too thin on one side. That thin side is where a voltage test or long-term ageing breaks through first.
Overall Diameter and Ovality
For sheathed round cables, two diameter readings are taken at the same cross-section. The difference between them must not exceed 15% of the upper limit for the mean overall diameter.
Ovality matters for glands and terminations. An oval cable won’t seal properly in a round gland.
Line 6: Mechanical Properties and Ageing
These tests check that the PVC is the right grade and will stay flexible over its life.
| Test | PVC/C (fixed) | PVC/D (flexible) | PVC/E (heat-resistant) |
|---|---|---|---|
| Tensile strength, as delivered, min | 12.5 N/mm² | 10.0 N/mm² | 15.0 N/mm² |
| Elongation at break, as delivered, min | 125% | 150% | 150% |
| Air oven ageing | 80 °C, 7 days | 80 °C, 7 days | 135 °C, 10 days |
| Max change after ageing | ±20% | ±20% | ±25% |
| Loss of mass, max | 2.0 mg/cm² at 80 °C, 7 days | 2.0 mg/cm² at 80 °C, 7 days | 2.0 mg/cm² at 115 °C, 10 days |
| Heat shock | 150 °C, 1 h, no cracks | 150 °C, 1 h, no cracks | 150 °C, 1 h, no cracks |
| Hot pressure, max indentation | 50% at 80 °C | 50% at 70 °C | 50% at 90 °C |
| Cold bending | −15 °C, no cracks | −15 °C, no cracks | −15 °C, no cracks |
The values in the table are medians.
What each one tells you:
- Ageing with change limits. PVC softens with plasticiser. Heat drives plasticiser out, and the PVC turns hard and brittle. A large drop in elongation after ageing means the compound won’t last.
- Loss of mass. This measures the same thing directly: how much plasticiser evaporates.
- Heat shock. Strained PVC cracks when heated. This catches over-stressed extrusion.
- Hot pressure. A blade presses into hot insulation. Too soft, and the conductor will push through the insulation where it’s clamped or bent tight in service.
- Cold bending. PVC becomes brittle in the cold. This checks it can be installed at −15 °C without cracking.
Line 7: Flexing Tests (Flexible Cords Only)
Flexible cables have to survive movement. The main test is the flexing machine.
- The cable runs over four pulleys. A carrier moves back and forth over 1 m at about 0.33 m/s.
- Weights keep it under tension.
- The cores carry current, and 230 V AC (two-core) or 400 V three-phase (three or more cores) is applied between them.
- The machine stops on a broken conductor, a short between cores, or a short to the pulleys.
Pass: 15,000 back-and-forth movements (30,000 strokes) with no break and no short. The sample must then pass the completed-cable voltage test.
The flexing test is for small flexible cords. It doesn’t apply to tinsel cords or to large-section flexibles, and the size limit is set in the method standard. Other mechanical tests on specific cord types:
- Bending test (tinsel cord): 60,000 cycles with no break in current, then 1500 V to water.
- Snatch test (tinsel cord): a 0.5 kg weight dropped five times from 0.5 m, with no break in current.
- Core separation (flat non-sheathed cords): the force to pull the cores apart must be between 3 N and 30 N. Too low and they split in use. Too high and an electrician can’t separate them without damage.
Line 8: Flame Retardance
All PVC cables in the series must pass IEC 60332-1-2, a vertical flame test on a single cable. It checks that one burning cable doesn’t carry the flame up its length.
It’s a single-cable test only. It says nothing about bunched cables in a riser, which is a separate test series.
Line 9: Markings
Printed markings are rubbed lightly ten times with cotton wool or cloth soaked in water. They must still be legible.
The manufacturer’s identification must repeat along the cable. The maximum gap between marks is 550 mm on the outer sheath. It’s 275 mm if the marking is on the insulation (sheathed or not) or on a tape inside a sheathed cable.
Production Line Tests
IEC 63294 also includes an “absence of faults” check, which is a spark test done to IEC 62230 as the cable runs off the line. A pulsed high-voltage source isn’t allowed for this. Pass means no faults detected.
This is how the factory screens every metre, not just samples. Lines 2 to 4 confirm the design on samples. The spark test catches the random pinhole in between.
Reading the Report: A Checklist
When a PVC wire test report lands on your desk:
- Which method standard? IEC 63294 for current work.
- Is the rating right? 450/750 V cable should show 2500 V on both voltage tests.
- Does thickness show both rules? You want the mean and the minimum, not just one.
- Check the IR conditions. Water temperature, soak time and DC voltage must be stated, along with the result in MΩ·km. A value with no temperature can’t be checked.
- Does the compound type match the application? PVC/C for fixed wiring, PVC/D for flexible cords, PVC/E for hot internal wiring.
- Does conductor resistance meet IEC 60228? Undersized copper is common and easy to catch here.
Quick Reference
| Test | Sample | Conditions | Level | Pass |
|---|---|---|---|---|
| Conductor resistance | ≥ 1 m | Corrected to 20 °C, 1 km | IEC 60228 max | Not above max |
| Voltage, completed cable | ≥ 10 m | 1 h in water, 20 °C | 2000 V (≤ 300/500 V), 2500 V (450/750 V), 5 min | No breakdown |
| Voltage, cores | 5 m | Sheath off, 1 h in water | 1500 / 2000 / 2500 V, 5 min | No breakdown |
| Insulation resistance | 5 m cores | ≥ 2 h in hot water | 80–500 V DC, 1 min | ≥ table value in MΩ·km |
| Insulation thickness | 3 pieces, ≥ 1 m apart | Each core | Mean ≥ specified | Min ≥ spec − (0.1 mm + 10%) |
| Ovality | 3 pieces | Same cross-section | – | ≤ 15% of upper diameter limit |
| Flexing | Flexible cords | 1 m stroke, 0.33 m/s, loaded | 15,000 cycles | No break or short |
| Flame | Single cable | Vertical, IEC 60332-1-2 | – | Pass |
| Marking durability | – | 10 rubs, wet cloth | – | Legible |
FAQ
Is IEC 60227-2 still valid? No. It was withdrawn in 2021 and replaced by IEC 63294:2021. The cable requirements are still in IEC 60227-1 and the other parts of the series.
Why is the minimum insulation resistance only 0.011 MΩ·km? Because it’s measured at 70 °C, in water, after at least 2 hours of soaking, and normalised to a full kilometre. Those are harsh conditions on purpose. On a 5 m sample, 0.011 MΩ·km is 2.2 MΩ.
Can I use these values for field testing a new installation? No. They are factory values for a specific hot, wet test. Field insulation tests on installed circuits use their own limits and conditions. For field methods, see cable insulation testing and how to use a megohmmeter.
What’s the test voltage for 450/750 V wire? 2500 V AC for 5 minutes, both on the completed cable and on the cores.
Why test in water? Water reaches the whole outer surface, so every pinhole or thin spot along the sample gets stressed. A fixed electrode would only touch part of it.
What’s the difference between PVC/C and PVC/D? PVC/C is for fixed installation. PVC/D is for flexible cables. They have different mechanical limits: PVC/D needs 150% elongation at break versus 125% for PVC/C, but allows a lower tensile strength.
Does insulation thickness have to be exact? The mean must meet the specified value. Any single point can be thinner, but by no more than 0.1 mm plus 10% of the specified value.
What’s a spark test? A high-voltage check that the whole length passes through as the cable is made. It catches random faults between the sample tests. Under IEC 63294, it follows IEC 62230 and doesn’t allow a pulsed source.
Does a PVC cable pass a fire test for bunched cables? Not necessarily. The series requires only the single-cable vertical flame test, IEC 60332-1-2. Bunched-cable fire tests are separate requirements.