Voltage Drop Calculator: Drop, Maximum Length and Minimum Size

By | October 28, 2026

Voltage Drop Calculator

Direct-on-line starts are typically 0.2–0.4.
Recommended Size: —
Max Length: —
Voltage Drop: —
Voltage Drop %: —
Voltage at Load: —
Starting Drop: —
Starting Drop %: —
 

Start with an example

A 50 A three-phase load at 400 V, power factor 0.85. Copper 16 mm² multicore, 100 m long, conductor at 75 °C.

Enter those values in Voltage Drop mode. The tool returns:

  • Voltage drop: 10.9 V
  • Voltage drop: 2.72 %

Now add a motor start current of 300 A (six times running current). Starting drop jumps to about 65 V, or 16 %. Fine for running, but the contactor might drop out on start. That’s the kind of thing this tool is built to show.

How it gets there

The tool uses the standard drop formula:

Vd = k × I × L × (R·cosφ + X·sinφ) / 1000

  • k = 2 for single-phase and DC, √3 for three-phase
  • R and X in Ω/km
  • L in metres

For DC, the reactance term drops out and the power factor is fixed at 1.

Resistance starts from a copper table at 75 °C. The tool converts it back to 20 °C, then forward to the temperature you pick (20, 75 or 90 °C). Aluminium is taken as 1.606 times copper resistance, with its own temperature coefficient.

Reactance depends on how the cores sit:

Cable typeReactance factor
Multicore1.00
Single-core, trefoil0.95
Single-core, flat1.10

Parallel runs divide both R and X by the number of runs.

Three modes, three questions

Voltage Drop. “I have this cable. What’s the drop?” Enter size and length.

Maximum Cable Length. “How far can I go with this size?” Enter size and the allowed drop. Useful when laying out a site and deciding where to put a sub-distribution board.

Minimum Cable Size. “What’s the smallest size that meets my drop limit?” Enter length and allowed drop. The tool walks up from 1.5 mm² to 300 mm² and stops at the first size that passes.

One warning on the last mode: it checks drop only. It does not check ampacity. On short runs it can suggest a size that’s too small for the current. Always check current rating separately.

The temperature setting and insulation

The operating temperature setting is not just a detail. It ties to the insulation.

A PVC cable at full load runs near 70 to 75 °C. An XLPE cable at full load can reach 90 °C. Copper resistance rises about 0.39 % per degree. Between 20 °C and 90 °C that’s over 27 % more resistance, and 27 % more drop.

So:

  • Lightly loaded cable: 20 °C is closer to reality.
  • Fully loaded PVC: use 75 °C.
  • Fully loaded XLPE: use 90 °C.

Picking 20 °C for a hot, loaded cable makes the drop look better than it will be.

Motor starting drop

Fill in Motor Start Current and the tool adds a second result: drop during start. Direct-on-line motors draw five to eight times running current. A cable that passes at 3 % running drop can see 15 % or more on start.

Note the tool uses the same power factor for starting. Real starting power factor is lower, often 0.2 to 0.4. On larger cables where X matters, starting drop can differ from the result. Treat it as an estimate.

FAQ

What’s a normal voltage drop limit?
Many designs use 3 % for final circuits and 5 % total from the origin. Check your local rules and your client spec.

Why is single-phase k = 2 and not 1?
Current flows out on the line and back on the neutral. Both conductors add drop.

Does the tool account for harmonics?
No. Heavy harmonic loads raise neutral current and effective resistance. Size those circuits with extra margin.

Why does trefoil have lower reactance than flat?
The cores sit closer together in trefoil. Less spacing means less loop area and lower inductance.

Can high voltage drop damage insulation?
Not directly. But undervoltage makes motors draw more current and run hotter, and heat is what ages winding insulation.

Author: Zakaria El Intissar

Zakaria El Intissar is an automation and industrial computing engineer with 12+ years of experience in power system automation, electrical protection, and SCADA systems. He founded InsulationTesting.com to share practical, field-tested guides on insulation resistance testing, equipment, and industry standards. His writing is used by electricians and maintenance engineers worldwide. Based in Morocco.