System Magnitudes Calculator
Compute positive, negative, and zero sequence components of three-phase voltages and currents using symmetrical component transformation. Ideal for power system engineers and SCADA analysis.
Voltages
Currents
Results
Three phasors are hard to read at a glance. Split them into sequence components and a fault or an unbalance becomes obvious. This tool takes phase voltages and currents (magnitude and angle) and returns U1, U2, U0 and I1, I2, I0, plus unbalance ratios and power factor.
What does each sequence tell you?
Positive sequence (U1, I1) is the normal, balanced system. In a healthy network it’s almost all you see.
Negative sequence (U2, I2) shows unbalance. Open phase, single-phasing, unequal loads, phase-to-phase faults. It also heats motor rotors, so motor relays watch it closely.
Zero sequence (U0, I0) shows current or voltage going to earth. On a site, that usually means an insulation failure somewhere.
What does an earth fault look like?
The tool loads with an example. Phase A at 3 V, phases B and C at 63.5 V, all at 120° spacing. That’s a 110 V secondary system with phase A almost shorted to earth.
Results:
- U1 ≈ 43.3 V ∠ 0°
- U2 ≈ 20.2 V ∠ 180°
- U0 ≈ 20.2 V ∠ 180°
U2 and U0 come out equal, in phase with each other. That’s the signature of a single-phase-to-earth fault. Healthy phases stay near normal, the faulted phase collapses, and zero sequence appears.
A quick guide to common patterns:
| Condition | U2 | U0 |
|---|---|---|
| Healthy, balanced | ~0 | ~0 |
| Single phase to earth | Present | Present, close to U2 |
| Phase to phase | Present | ~0 |
| Three-phase fault | ~0 | ~0 |
| Unbalanced load | Small | ~0 |
Where does insulation testing fit?
A rising U0 on a resistance-earthed or isolated network often comes before a full fault. Insulation is breaking down on one phase and starting to leak. If your SCADA or relay records show creeping U0, run IR tests on the feeders before it becomes a trip.
On isolated (IT) systems, a single earth fault doesn’t trip anything. U0 jumps, and the system keeps running. The second fault is the one that does damage. Sequence values help you find the first one early.
What do the unbalance ratios mean?
The tool gives:
- U2/U1 %: voltage unbalance. Many specs limit this to around 2 % at the supply point. Motors start losing life above that.
- U0/U1 %: how much earth component there is compared to the normal system.
- I2/I1 % and I0/I1 %: the same for current.
What about the power factor lines?
Per-phase power factor is cos(voltage angle − current angle) for each phase. Three-phase power factor is total P divided by total S. Use per-phase values to spot a phase with a wrong CT polarity or a swapped VT. One phase reading the opposite sign of the others is the usual giveaway.
What input mistakes break the result?
Using line-to-line voltages. Zero sequence only exists in phase-to-earth values. Line-to-line voltages always sum to zero, so U0 will always show zero. Enter phase-to-neutral or phase-to-earth.
Wrong angle reference. Pick one phasor as 0° (usually UA) and measure everything else from it.
I0 vs 3I0. The tool gives I0. Relays and residual CT connections measure 3I0, the sum of three phase currents. Multiply by three before comparing to a relay setting.
FAQ
Which sequence convention does the tool use?
Standard ABC rotation with operator a = 1∠120°. U1 = (UA + a·UB + a²·UC)/3.
Can I use primary or secondary values?
Either. Stay consistent across all three phases.
Why is there negative sequence on a healthy system?
Supply unbalance and unequal single-phase loads. A small amount is normal.
Does zero sequence current always mean an insulation fault?
Not always. Third harmonics in the neutral also show as zero sequence. Check the frequency content before assuming a fault.
Is the tool usable for relay testing?
Yes, for checking expected values before injecting with a test set.