Tan δ is a small number measured against a demanding background. You are resolving a resistive current a thousand times smaller than the capacitive current beside it, at high voltage, with stray capacitance to earth trying to corrupt the reading. The instrument matters. IEC 60034-27-3 recognizes three ways to make the measurement, and each one exists to solve a specific problem the others left open.
This is the instrumentation side of the dissipation factor test. What all three share: a variable-amplitude AC supply rated to drive the test object’s capacitance and complying with the requirements of IEC 60060-1 and IEC 60060-2, and a near-lossless high-voltage standard capacitor used as the reference.
Table of Contents
What the measurement is actually resolving
The insulation current splits into a capacitive part that leads the voltage by 90° and a small resistive part in phase with it. Model the insulation as a capacitance in series or parallel with a resistance. For the series equivalent circuit, tan δ = ωCsRs; for the parallel equivalent circuit, tan δ = 1 / (ωCpRp), where ω = 2πf.
The capacitance is the lossless part of the insulation; the resistance lumps together every loss mechanism. Every instrument below is, at bottom, a way to compare the test object against a known-lossless reference capacitor and extract that resistive component. The reference capacitor is therefore critical — its own dissipation factor has to stay below 0.01 × 10⁻³ across the full test voltage, or it pollutes the very quantity you’re measuring.
The Schering bridge
The classic high-voltage method. The test object and a high-voltage standard capacitor form the two high-voltage arms of a bridge; the low-voltage side carries precision variable resistive and capacitive decades (R1, R2, C1). You balance the bridge — adjusting the low-voltage elements until a sensitive null indicator reads zero — and the balance condition gives you both capacitance and tan δ. Most modern Schering bridges automate that balancing.
Its weakness is its sensitivity. The Schering bridge is very sensitive to disturbances from stray capacitance to earth, which is exactly what surrounds a high-voltage test setup. The fix is double-screened coaxial measuring cables with an active screen-potential compensator — a Wagner earth circuit — to hold the screen at the right potential and keep stray paths out of the measurement. Without adequate screening and compensation, stray capacitance can influence the measurement.
The reference standard capacitor is typically 100 pF or 1000 pF, with a long-term capacitance tolerance of less than 5%, and that sub-0.01 × 10⁻³ dissipation factor.
The transformer ratio-arm bridge
The second analogue method removes the Schering bridge’s biggest inconvenience. Instead of resistive and capacitive decades, it uses a current comparator: the standard capacitor and the test object each drive windings, wound in opposite directions, around a high-permeability magnetic core. You balance the bridge by adjusting the turns ratio and an adjustable resistor until the magnetomotive force in the core is zero.
At balance, the potentials that stray capacitances would act on collapse to virtually zero — so stray capacitance to ground stops influencing the result. The practical payoff is direct: the transformer ratio-arm bridge does not need the Wagner earth circuit the Schering bridge requires. Same job, one less thing to set up and get wrong.
Digital phase-shift systems
The modern method, and the most flexible. High-resolution analogue-to-digital conversion and digital filtering let a computer-controlled system measure tan δ directly from the currents rather than by nulling a bridge.
It records the current through the reference capacitor and the current through the test object simultaneously, using the high voltage as a timing reference, and computes tan δ from the phase difference between them. The digital approach brings several things a bridge can’t:
- Simultaneous high-precision measurement of current and voltage in both high-voltage paths.
- Digital filtering that suppresses harmonics and external noise, in the time or frequency domain — valuable in an electrically noisy plant.
- Direct calculation and live display of tan δ and capacitance against the applied voltage, throughout a computer-controlled voltage ramp.
The most useful capability for field work comes from isolating the measuring electronics at high potential with fiber-optic data links. Because the fiber acts as a high-voltage insulator, battery-powered measuring devices can sit at test potential and measure permanently earthed machines in the field — a stator that stays bonded to its frame, tested on site during an outage, without lifting grounds. An analogue Schering bridge can measure a solidly grounded machine too, but it needs an auxiliary pass adapter to avoid operating ungrounded — an extra measure the digital arrangement sidesteps.
Choosing among them
They measure the same quantity; they differ in setup burden and where they’re used.
- Schering bridge — the reference method, accurate and well understood, but it needs the Wagner earth and careful screening. Common in laboratories.
- Transformer ratio-arm bridge — the same analogue accuracy without the Wagner earth, because the current comparator rejects stray-capacitance effects inherently. Less setup.
- Digital phase-shift system — computer-controlled, noise-filtered, live-reading, and with fiber-optic isolation a particularly practical way to measure a permanently earthed machine on site. The usual choice for modern field and production testing.
Whatever the instrument, the test procedure still governs the conditions that make the number meaningful: a sinusoidal AC voltage applied in controlled steps from 0.2 UN toward rated voltage, ambient temperature in air, and appropriate guarding for individual bars and coils. The instrument changes how you resolve tan δ, not the conditions under which the number means something.
FAQ
How is tan delta measured?
By comparing the test object against a near-lossless reference capacitor at high voltage and extracting the small in-phase resistive current. IEC 60034-27-3 recognizes three instruments: the analogue Schering bridge, the transformer ratio-arm bridge, and digital phase-shift measuring systems.
What is a Schering bridge?
A high-voltage bridge that balances the test object against a standard capacitor using precision resistive and capacitive decades, giving capacitance and tan δ at the null point. It is very sensitive to stray capacitance and needs a Wagner earth circuit and screened cabling.
What is a Wagner earth and why is it needed?
An active screen-potential compensator used with double-screened coaxial cables to hold the screen at the correct potential, keeping stray capacitance to earth out of the measurement. The Schering bridge needs it; the transformer ratio-arm bridge does not.
How does a transformer ratio-arm bridge differ from a Schering bridge?
It uses a current comparator around a magnetic core instead of resistive/capacitive decades. At balance the magnetomotive force is zero, which cancels the effect of stray capacitance to ground, so it doesn’t require a Wagner earth.
Can tan delta be measured on a machine that stays earthed?
Yes, with a digital phase-shift system using fiber-optic data links. The fiber acts as a high-voltage insulator, so battery-powered electronics can sit at test potential and measure a permanently earthed machine in the field during an outage.
Why does the reference capacitor have to be so low-loss?
Because the measurement compares the test object against it. If the reference capacitor’s own dissipation factor isn’t below 0.01 × 10⁻³ across the test range, it corrupts the tan δ you’re trying to read.